Description
Product Name | GW100UV Ultraviolet Flame Detector | GW100IR2N Dual-Band Infrared Flame Detector | |
Product Images | |||
Performance Characteristics | Wide Field of View,Long Distance | Wide Field of View,Short Distance | |
Fields of Application | Industrial Workshops | Machines,Equipment,Small Spaces | |
Detection Angle | ≥120° | ≥100° | |
Fire Source Situation | Detection Distance (Unit: m) | Detection Distance (Unit: m) | |
Gasoline |
0.1m² Fire Disk (0.3m x 0.3m) | 40 | 40 |
n-Heptane | 50 | 45 | |
Diesel Fuel | 40 | 40 | |
Kerosene | 40 | 40 | |
Aviation Kerosene | 40 | 40 | |
Alcohol | 40 | 35 | |
Isopropanol | 40 | 35 | |
Methanol | 35 | 30 | |
Polypropylene | 25 | 20 | |
Paper | 30 | 30 | |
Methane | 0.5m(h) x 0.2m(w) Gas Flame | 25 | 35 |
LPG Propane | 25 | / | |
Hydrogen | 25 | / | |
Ammonia | 20 | / | |
Silane | 0.3m Flame | 15 | / |
Aluminum and Magnesium Metal | 15 | / | |
The size of the Fire Disk | Response Time | ||
0.3m x 0.3m Gasoline Fire | ≤20 Seconds (High-Speed Type ≤ 1 Seconds) | ||
0.7m x 0.7m Gasoline Fire | <10 Seconds | ||
Hydrogen Flame or Metal Flame | / | ||
Output Mode | 2 Relays Output | ||
Working Voltage | DC24±6V | ||
Working Environment | -10℃~55℃ (Ordinary Type) or -40℃~70℃ (Enhanced Type) 0~95%RH (Non-Condensing) | ||
Explosion Proof Certification | Exd II CT6 Gb | ||
Ingress of Protection | IP66/IP67 | ||
Electrical Interface | 1 x NPT 1/2 | ||
Housing Material | Cast Aluminum | Cast Aluminum | |
Dimensions | 72mm x 72mm x 96mm | 60mm x 60mm x 68mm | |
Weight | 0.5kg | 0.4kg | |
Certification | CCC、SIL2、SIL3 | CCC |